5.6.2.1 Initialising OPAL Devices
OPAL protocol loop devices need programming, or
initialising, before the panel can perform a learn operation
and permit device polling. Device initilialisation is normally
performed as part of a learn operation. However,
initialisation can be carried out independently of a learn
operation, for example after the replacement of a loop
device, as described below.
Also, it is possible to display the loop device totals,
normally displayed after a learn operation, using the
LEARN menu option '4: Display Totals'.
1 Use the '
/
2
8
display.
[S1 LEARN]
3 : Display Totals
4 : Initialise OPAL
2 Press the '
' pushbutton using the numeric keypad
4
to select 'Initialise OPAL'. A request for initialise
confirmation is then displayed:
[LEARN]
Confirm OPAL Device Initialise
3 Press the '
5
initialisation or press '
[Learn] Initialising OPAL Devices
4 When initialisation is complete the second menu
screen is re-displayed:
[S1 LEARN]
3 : Display Totals
4 : Initialise OPAL
Note: If this option is selected before a learn operation is
carried out or with a CLIP protocol loop the
following error message is displayed:
[LEARN]
No OPAL Devices Configuration
5 To re-display the learn totals after an initialise
operation, use the numeric keypad and press the '
button to select the option 'Display Totals':
[LEARN] Total 010 (003 + 007)
OPAL:
OPT 03,
SM2 02, SM3 01, M701 01
78
' buttons to scroll to the second menu
: More
: Continue <: Cancel
' pushbutton to confirm device
' to cancel:
4
: More
<: Exit
: More < : Exit
'
3