Honeywell Notifier ID50 Installation, Commissioning & Configuration Manual page 69

Hide thumbs Also See for Notifier ID50:
Table of Contents

Advertisement

ID50 Series Panel - Installation, Commissioning & Configuration Manual
5
or
2
8
6
5
or
2
8
5.5.5.5 Heat Det. End Delay
The Day Mode function, Delays to outputs, can be
cancelled when a heat sensor goes into alarm. To select
the Heat Det. End Delay option:
[S1
Setup]
1: Panel Options
2: Site Details
3: Device Options
[S1
Setup]
5: Day / Night Settings
1 From the Setup menu screen, press the '
on the numeric keypad to enter the Day/Night Settings
menu. The Day mode activity screen is displayed first.
[Setup]
Day mode activity = DISABLED
> : Change
1 : Disable
2 Press the '
/
2
Night Settings options until the Heat Det. End Delay
screen is displayed.
[Setup]
Heat Det. End Delay = No
> : Change
3 Press the '
' button to toggle this function.
6
[Setup]
Heat Det. End Delay = Yes
> : Change
4 Press '
' to exit and return to the Setup menu
4
screen. The selection is saved on exiting.
5.5.5.6 Day Mode 2 Zone Ends Delay
The Day Mode function, Delays to outputs, can be
cancelled, through this Day/Night Settings option, by a
second zone going into alarm. This is an alternative to a
second device in the same zone going into alarm or the
activation of an MCP cancelling active delay timers.
To select the Day Mode 2 Zone Ends Delay option:
[S1
Setup]
1: Panel Options
2: Site Details
3: Device Options
[S1
Setup]
5: Day / Night Settings
1 From the Setup menu screen, press the '
on the numeric keypad to enter the Day/Night Settings
menu. The Day mode activity screen is displayed first.
[Setup]
Day mode activity = DISABLED
> : Change
1 : Disable
2 Press the '
/
2
Night Settings options until the Day Mode 2 Zone Ends
Delay screen is displayed.
[Setup]
Day Mode 2 Zone Ends Delay
> : Change
65
: More
4: Peripheral Options
: More
< : Exit
' buttons to step through the Day/
8
: More
< : Exit
: More
< : Exit
: More
4: Peripheral Options
: More
< : Exit
' buttons to step through the Day/
8
= No
: More
< : Exit
997-263-000-11, Issue 11
January 2010
: More
' button
5
: More
' button
5