Honeywell Notifier ID50 Installation, Commissioning & Configuration Manual page 74

Hide thumbs Also See for Notifier ID50:
Table of Contents

Advertisement

ID50 Series Panel - Installation, Commissioning & Configuration Manual
SMART 4 Devices
The mult-criteria sensor SMART 4
logical device type, depending on loop
protocol, is SM4 (CLIP) or SMT4
(OPAL).
or
1
2
3
997-263-000-11, Issue 11
January 2010
5.6.1.2 Sensor Sensitivity Setting
This option allows the sensitivity of sensors to be changed
during device configuration. Access is via the Circuit menu.
Individual sensor Alarm and/or Day settings can be changed.
VIEW
TM
Sensors and SMART 4 Multi-Sensors
The ID60 Panel supports VIEW
Appendix 2, ID60 Single Loop Panel Differences.
Co-operative Multi-sensing Groups
The ID60 Panel supports co-operative multi-sensing through
the Advance Warning Addressable Combustion Sensing
(AWACS
TM
VIEW
, ION, OPT, MLT, OPX/SM2 (Optiplex Multi-Sensor),
TM
SM3, SM4, (SMART 3 and 4 Multi-criteria Sensors). Once
included in the AWACS
configuration follows that for VIEW
levels and not a percentage of alarm. During configuration
of the sensor sensitivity values, the LCD returns to the
previously configured value if any of the following occurs:
a. The '
4
b. The panel state is unchanged for 1 minute.
c. A value outside the predefined operating limits (80% to
120% or L1 to L6 for OPX/SM2, SM3 or SM4) is entered.
To change the sensor sensitivity settings:
1 At the sensor attributes menu, press the '
on the numeric keypad to display the Sensor Sensitivity
Setting menu:
[Sensor nn - AAA] Sensitivity
1: Alarm (100%)
2 Using the numeric keypad, press '
setting or press '
1
[Sensor nn - AAA] Sensitivity
2
Enter new alarm level : 120
[Sensor nn - AAA] Sensitivity
Enter day mode alarm : 80
3 At the appropriate prompt, use the numeric keypad to
enter the desired percentage value. Press '
confirm the value entered.
[Sensor nn - AAA] Sensitivity
1: Alarm (120%)
4 Press '
the appropriate prompt, use the numeric keypad to
enter the desired AWACS group:
[Sensor nn - AAA] Sensitivity
Enter new AWACS Group : _
5 Press '
press '
70
TM
and SMART 4. See
) software algorithm for the following devices:
TM
algorithm, the sensitivity
TM
device types, i.e. using
' button on the numeric keypad is pressed.
2: Day (100%) 3: Group (00)
' to select the Alarm Sensitivity
1
' to select the Day Mode Sensitivity setting:
2
< : Cancel
2: Day (80%)
3: Group (00)
' to select a new AWACS group, if required. At
3
' to confirm the AWACS group entered or
5
' to cancel.
4
' button
3
< : Cancel
' to
5
< : Cancel