Assembling The Panel - Honeywell NOTIFIER ID62 Installation, Commissioning & Configuration Manual

Hide thumbs Also See for NOTIFIER ID62:
Table of Contents

Advertisement

ID61/62 Series Panel - Installation, Commissioning & Configuration Manual
1 & 5
1 & 5
2
7
9
JP6
JP6
E_FLT
E_FLT
9
JP7
JP7
MEM
MEM
ii
iii
iv
i
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
xii
CRYSTAL
FREQUENCY (XT2)
124-391 ID50+ PCB
x
xi

2.6 Assembling the Panel

With the back box secured to the wall and all external cabling
ready for termination, assemble the panel as follows:
1 Ensure that all power to the panel is isolated and
observe ALL safety and anti-static precautions when
installing the PCB assembly.
2 Taking suitable anti-static precautions, offer the four slotted
holes of the chassis to the back box and, with it adequately
supported, connect the chassis earth lead to the earth blade
connectors in the back box.
3 Locate the back box on the M4 SEM screws. Once in position,
use a cross-headed screwdriver to tighten the screws.
4 Fit the labels. They may require the application of a
low tack adhesive:
i
Apply low tack adhesive to hatched area indicated.
ii Slide each label into position.
iii Apply slight pressure to the area along the bottom
edge of the fascia to ensure the labels are secure.
5 Insert the IEC mains plug into the socket on the top of
the PSU and apply mains power supply - then connect
the batteries. Check the PCB assembly operates
correctly and then isolate all power to the panel.
6 At the Main PCB assembly:
i
Noting the cable polarity, connect all cables and
secure at the correct termination blocks, see Cables
& Wiring below.
ii Set all required hardware jumper configurations,
refer to the Section 4 Commissioning.
7 Fit the RS485 Interface Module PCB, if applicable, refer to
Section 2.7 RS485 Communications Link.
8 Re-apply the mains power supply and then connect
the batteries.
4
9 Disconnect the links at the earth fault monitoring jumper
E_FLT (JP6) and configuration lock MEM (JP7). Then
connect the RS232 9-way 'D' type Data Transfer Lead
(PN 082-173) to the panel at the RS232 socket
8
connector, SK3. Using the Support Tool, transmit the
+
-
TE M
latest system configuration to the panel.
P SN
SR
10 Remove the lead and fit the links at JP6 and JP7, then
fit the cover.
Note: Connect the earth wire to the inner side wall of the
cover at the tag marked with the earth symbol.
Cables & Wiring
vi
v
i
ii
iii
7
8
9
iv 24 V Auxiliary Power Supply (TB4)
4
5
[
6
v
1
2
3
vii
0..9
0
vi -VE Outputs (TB6)
vii Keyswitch
viii PSU Input (SK4, SK5)
ix
x
viii
xi RS232 Port (printer option)
xii RS485 Communications Cable (SK1).
ix
viii
15
ÜE/Sounder Output A and Sounder Output B (TB1)
CFG Outputs C and D (TB2)
Digital / ÜE Inputs (TB3)
Loop Cable Output/Input (TB5)
FBF Communications Cable (TB9)
FBF Power Supply (TB8)
997-457-000-8, Issue 8