5.6.3 On-Board Circuits

This option permits configuration of the On-Board Output
Circuits. There are six output circuits as defined in the
following table:
Description
Monitored Sounder (SDR or SDH) or Monitored Control
Module (CTL) or Transmission Device (TxD) can be
programmed for Fire Alarm, Fault, Pre-Alarm, Plant
Warning or Extinguishing System CBE Rules.
Factory Default = Fire Alarm - All Zones.
Monitored Sounder (SDR or SDH) or Monitored Control
Module (CTL) can be programmed for Fire Alarm, Fault,
Pre-Alarm, Plant Warning or Extinguishing System CBE
Rules.
Factory Default = Fire Alarm - All Zones.
Can be configured for operation as a Monitored Output
(Sounder Circuit or Relay Circuit) or as an Unmonitored
Output (volt-free style relay Circuit).
Can be programmed for Fire Alarm, Fault, Pre-Alarm,
Plant Warning or Extinguishing System CBE Rules.
Factory Default = Unmonitored Relay.
Can be configured for operation as a Monitored Output
(Sounder Circuit or Relay Circuit) or as an Unmonitored
Output (dry-contact style relay Circuit).
Can be programmed for Fire Alarm, Fault, Pre-Alarm,
Plant Warning or Extinguishing System CBE Rules.
Factory Default = Unmonitored Relay.
Unmonitored Output Circuit. Can be programmed for Fire
Alarm, Fault, Pre-Alarm, Plant Warning or Extinguishing
System CBE Rules.
This output is normally used to drive an external relay.
Factory Default = General Pre-Alarm
Unmonitored Output Circuit. Can be programmed for Fire
Alarm, Fault, Pre-Alarm, Plant Warning or Extinguishing
System CBE Rules.
This output is normally used to drive an external relay.
Factory Default = Plant Warning
To change the On-Board Output CBE rule:
1 Press '
' on the numeric keypad, select the
2
On-Board menu from the Circuit Menu below.
[S1 Circuit]
1 : SLC Loop 2 : On-Board
2 The display then shows the following menu. Select
the appropriate action:
[ON-BOARD]
B01 (SDR)
1 : Type
2 : CBE Rule (01)
a. Using the numeric keypad press '
Type of output, or
b. Press '
' on the numeric keypad to change the CBE
2
Rule with which the On-board output is associated.
c. Use the '
/
2
8
number and its associated CBE Rule.
d. Press the '
' on the numeric keypad to toggle the
3
monitoring end-of-line device type: resistor (default
setting) or diode.
e. Press the '
' to Cancel and return to the Circuit menu.
4
79
3: Mon. : RES.
: Change < : Exit
' to change the
1
' to change the On-board output
997-263-000-11, Issue 11
January 2010