ID50 Series Panel - Installation, Commissioning & Configuration Manual
CBE nn [THERMAL][ANY] 1 - - - - - - - - - - - - - - - - - - - - 1 6
1 : Change
[EvSlln
CBE nn [ES SYSFLT]
1 : Change
EN54-2 : 7.11.d.
Configured delays MUST
be set to interruptable
(Y) to remain EN54
compliant.
997-263-000-11, Issue 11
January 2010
d.
] YYYYNNYYYYYNYYNN
e.
Each of the CBE Output Rules has various configurable
states available, dependent on the rule type. These states
are described below:
a. Filter-by-type - options are ANY (all types), OTI
(Optical, Thermal, Ionisation, MULTI /OPX/SM2, SM3
or SM4 [ID60 only] sensor), AVS (ID60 only - see
Appendix 2), MCP (manual call point), MON (monitor
module). Extinguishing System options are
Smoke/Heat, Sensor/MCP, VIEW/Sensor, Any Two
Zones, Any Two Sensors, Any Single Sensor and Any
Single Module. Output will only operate if the input is
received from a device of the selected type.
b. Evacuate (EV) - has two options Yes (Y) or No (N). If
set to Y(es) assigned outputs activate when the END
DELAYS/EVACUATE pushbutton is operated. Outputs
will not operate when this option is set to N(o).
c. Silenceable (SL) - has two options Yes (Y) or No
(N). If set to Y(es) assigned outputs will silence when
the SILENCE / RESOUND pushbutton is operated.
If set to N(o) the outputs will only silence after being
activated when the RESET pushbutton is operated.
d. Interruptable (IN) - has two options Yes (Y) or No (N). If set
to Y(es) operating the END DELAYS/EVACUATE pushbutton
cancels currently operating delays and assigned outputs
activate. If set to N(o), delays are NOT interruptable. The
delays can only be cancelled by another qualifying alarm
condition. This configuration does not comply with EN54
regulations.
e. Class Change (Cl) - has two options, Yes (Y) or No
(N). If digital input 1 is set to Class Change (see
Section 5.5.3.4) and the CBE Class Change option
is set to Y(es), then the assigned outputs operate
when digital input 1 is made. If set to N(o), digital input 1
(set to Class Change) does not operate the assigned
outputs.
f. Two Zone (Tz) - has two options Yes (Y) and No (N).
If set to Y(es), at least two zones must be active
before the CBE rule is triggered.
g. Zones - determines the output response to fire or
plant alarms on a zone by zone basis using two
options: Zones 01 to 16 and Zones 17 to 32.
i
Zones 01 to 16 - addresses the Fire rule silence
options. Each zone can be configured as:
N(o) - the zone is NOT included in the CBE Rule,
outputs will NOT be activated.
Y(es) - the zone is included in the CBE Rule. An alarm
in this zone activates the outputs immediately.
82
Thermal Mode rule (ID60 only). This CBE rule activates
assigned outputs when the thermal element of multi-criteria
devices (OPX/SM2, SM3 and SM4) goes into alarm.
Extinguishing System - System Fault. This CBE
rule lights the Extinguishing System Fault LED, if
provided, when a PLANT Alarm zone, with AUX
action EXT. SYSTEM FAULT, has been activated.