ID50 Series Panel - Installation, Commissioning & Configuration Manual
CAUTION:
This product is not compliant
EN
EN
12094-1
12094-1
with EN 12094-1.
!
!
Fire extinguishing installations in
Europe are required to be certified as
compliant to this standard.
3
5
or
2
8
(D)elay - the zone is included in the CBE Rule. An
alarm in this zone will activate outputs after a delay.
Not available for Fire rules if Two Zone is selected.
Extinguishing System rules default to Delay.
(C)oincidence - the zone is included in the CBE Rule.
Two alarms in this zone will activate outputs.
(P)ulsed - the zone is included in the CBE Rule. An
alarm in this zone will activate outputs immediately
in pulsed mode. This mode is overridden if an alarm
occurs in any zone that is included in this rule and for
which Pulse Mode is not selected, also if a device is
assigned to multiple CBE rules and a rule for which
Pulse Mode is not selected becomes active.
ii Zones 17 to 32 - addresses the plant warning rule
silence options. These zones can be configured in
the same manner as described for zones 01 to 16.
h. Soak Timer (Sk Tmr) - has two options Yes (Y) or
No (N). If set to Y(es) the associated extinguishing
output is active only for the time specified in the
System Soak Timer Setup menu.
To select the CBE Rule menu, proceed as follows:
1 With the Commissioning menu displayed, press the
'
' button on the numeric keypad.
3
[S1 COMM]
1 : Setup
3 : CBE Rules
4 : Zones 5 : Access
2 The LCD prompts you to enter a CBE Rule number
as shown below:
[CBE Rule]
Select Rule No ____
Enter the required CBE Rule number using the numeric
keypad and confirm by pressing the '
3 The LCD then displays the selected CBE Rule's current
configuration and a menu option to allow changes to
the rule. The displayed configurable options depend
upon the rule type. To change the rule configuration
press the '
' button on the numeric keypad.
1
CBE 01[FIRE
][ANY] 1 - - - - - - - - - - - - - - - - - - - - 1 6
1 : Change
[EvSlln
Note: You can use the '
each of the 64 CBE Rules.
4 At the menu below, use the numeric keypad to select
the option that requires changing.
CBE Rule:01
1:Type
4:Silence
5:Interrupt
CBE Rule:01
6:Class Change
9:Zones
Note: Selectable options are dependent upon the type
of the current CBE Rule.
83
2 : Circuit
: More
' button.
5
] YYYYNNYYNDDNCCNN
/
' buttons to step through
2
8
2:Filter
3:Evac
: More
7:Two Zone
: More
997-263-000-11, Issue 11