Cfg Outputs C And D - Honeywell Notifier ID50 Installation, Commissioning & Configuration Manual

Hide thumbs Also See for Notifier ID50:
Table of Contents

Advertisement

ID50 Series Panel - Installation, Commissioning & Configuration Manual
EN 54-2 : 7.7.1
One output must be
configured as a fire
output.
EN 54-2 : 7.8
If an EN54-2 monitored sounder
output is required an unmonitored
relay is not suitable. Use a
monitored sounder output.
EN 54-2 : 8.8
Either a relay
sounder output
configured as a fault
output.
1
These outputs are not monitored and
they should not be used as a fault
routing output (EN 54-2: 8.9).
J1 & J2
1
2
3
4
5
6
7
8
CFG Outputs C and D have
a default configuration of
unmonitored relay outputs
(see next page).
997-263-000-11, Issue 11
January 2010

4.4.5 CFG Outputs C and D

CFG Outputs C and D can be configured as sounder or
relay output circuits using configurable jumper links.
Output C is configured using jumper link J1 and Output
D is configured using jumper link J2.
The link settings for J1 and J2 are defined in the table
below. These changes must only be made with the system
powered down and become effective automatically on
power-up.
CFG Outputs C and D can be connected as:
a. Monitored Sounder Circuits, or
or a
1
b. Un-monitored Relay Outputs
may be
1
Note: A sounder output can be used to drive an external
relay to provide a monitored relay output.
Before connecting CFG Outputs C and D to the PCB
assembly, the appropriate hardware links may need to
be set.
CFG
OUTPUT
Output C
(default un-
monitored NC)
Output D
(default un-
monitored NO)
Fault Relay - In the panel's quiescent state a relay
configured as a fault relay is energised. Make the
appropriate '+' and '-' wiring connections.
Sounder Circuits
If these connections are to be configured as sounder
circuits make sure:
a. The 6k8 end-of-line resistors
to the end of the circuit, and
b. Correct polarity is used when terminating at the back
box, i.e. terminal 1 being positive and terminal 2 being
negative.
Monitored Remote Relay /Fire Routing Outputs
If these connections are to be configured to monitor for
open and short circuits make sure:
a. The 6k8 end-of-line resistors
to the end of the circuit, and
b. Correct polarity is used when terminating at the back
box, i.e. terminal 1 is positive and terminal 2 is negative.
c. A blocking diode is connected in series with the relay coil.
d. A back-emf diode should be connected across the
relay coil.
1
Alternatively, for partial-open- and partial-short-circuit
monitoring use one of the diodes supplied with each sounder
circuit in place of the 6k8 resistor.
30
Fit Jumper Sounder/
For
Links Over: Remote
Unmonitored
Relay
Normally-Open Normally-Closed
J1
1 & 3
1 & 2
4 & 6
3 & 5
5 & 7
7 & 8
J2
1 & 3
1 & 2
4 & 6
3 & 5
5 & 7
7 & 8
are correctly connected
1
1
are connected correctly
For
Unmonitored
1 & 2
5 & 6
7 & 8
1 & 2
5 & 6
7 & 8

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Notifier id60

Table of Contents