51 - Parameters (cont'd)
26 = Forced (Galaxy 18, 60, 128, 500 & 504)
The Forced parameter enables or disables Menu option 14 = FORCED SET. If the parameter is set to 1
(enabled) the user can force the system to set, automatically omitting any omittable zones that are open at the
time of setting. If the parameter is set to 0 (disabled), option 14 = FORCED SET is not available to the user;
the message Option not available is displayed. The parameter defaults to 0 (disabled).
NOTE: It is recommended that Final, Entry and Push-Set zones have the omit attribute disabled.
27 = CCT Debounce (Galaxy 18, 60, 128, 500 & 504)
The cct Debounce parameter determines the response time of the zones (how long they must remain open
before registering as changing state). The cct Debounce is programmable within the range 20–1000 millisec-
onds (0.02–1 second); the default is 300 msecs. All entries are rounded up to the nearest 20 msecs.
28 = Online Print (Galaxy 18, 60, 128, 500, 504 & 512)
This parameter is used to select the print mode required when connecting a serial printer to the Galaxy panel;
there are two options:
0 = disabled (default): system only prints specific details at the user's request. The printer can be
connected and disconnected at any time as required;
1 = enabled: this option switches the printer to on-line mode and requires that a printer be
continuously connected to the system. Events are printed as and when they occur. The events printed
are controlled by parameter 29 = Online Level.
NOTE: If Online Print is enabled, the event log and other options will not be printed at the user's request.
The parameter must be disabled to permit all other print options to operate.
29 = Online Level (Galaxy 18, 60, 128, 500, 504 & 512)
The On-line Level parameter determines the level of events that are printed when parameter 28 = Online
Print is enabled:
0 (default) - basic print (setting, unsetting, alarms);
1
- full print excluding MAX events (setting, unsetting, alarms, modifications, technical
details)
2
- full print including MAX events.
3
- MAX events only.
4
- Basic Print plus MAX events.
NOTE: If Online Level is set to 1 (exclude MAX events), then all MAX events in the log are not included
in the printout; if 2 (include MAX events) is selected, then the MAX events in the log are included in
the print.