56 - Communications (cont'd)
2 = Mode
This option controls access authorisation and whether the remote session is initiated from (Panel or PC).
1 = Direct Access
This permits access at any time (in conjunction with Access period). Access is initiated from Galaxy Gold.
Once access is authorised/initiated, uploading, downloading and remote servicing can begin.
2 = Manager Authorise
This option requires authorisation from the site manager in order to gain remote access to the Galaxy panel.
There are two methods that the manager user can use to enable access to the Galaxy via Galaxy Gold.
Timed Access – Galaxy Gold must access the Galaxy panel within 40 minutes of this option being enabled by
the manager (Option 47.1.2.0). Once connected there is no time limit on the access period. On terminating the
connection, Galaxy Gold can reaccess the system within a 15 minute period of the termination.
Call Back – the manager instructs the Galaxy panel to initiate a connection to the Galaxy Gold PC (Use option
47.1.2.1) by selecting one of the Call back IP addresses programmed into the system
1 = Call Back IP 1-5
There are 5 possible IP address/Port number destinations, which can be programmed for Galaxy Gold
access. This allows communication with up to 5 different Galaxy Gold locations.
1 = IP Address
Enter the IP address of the PC running the Galaxy Gold application
2 = Port No.
Enter the Port Number allocated to Galaxy Gold on the PC (Default is 10001)
04 = Autotest
An engineer test can be automatically transmitted to the receiving station at programmed intervals.
1 = Start Time
The engineer uses this option to enter the time that the first engineer test is transmitted. Subsequent engineer
test transmissions are sent periodically. The frequency of each test is controlled by the 2=Interval option.
2 = Interval
This option determines the period between automatic engineer test transmissions following the Start Time. The
programmable range is 0-99 hours.
05 = Engineer Test
An engineer test can be sent on each of the transmission paths once the appropriate IP address/port no, and
account numbers have been programmed into the system. This allows the installation engineer to ensure that
the receiving station is correctly receiving the events from the Ethernet module.
On selecting this option a warning message is displayed on the keypad, WARNING!!! ENT=SEND MES-
SAGE. Press the ent key to send the engineer test.
Galaxy Programming Manual
130