17 Link
This zone type has no operational function; it is designed to be used as a source of a link - refer to option 54 =
LINKS. The activation (+) and de-activation (–) of Link zones is recorded in the event log.
NOTE: option 54 = LINKS is not available on the Galaxy 8.
18 Spare
The Spare function allows any zones that are not being used to be ignored by the system; the resistance
readings from the circuit - including the tamper conditions - do not activate an alarm condition.
NOTE: It is recommended that all unused zones are programmed as Spare and that a 1kΩ 1% resistor is
connected across each of these zones.
19 Fire
The Fire function is continuously operational. When activated, a FIRE zone overrides the Bell Delay pa-
rameter and activates an instant alarm (Bell, Strobe and Fire). The keypad buzzer and control panel horn
output, if fitted, emit an interrupted tone (one second on, 0.5 seconds OFF), easily distinguishable from all
other alarm conditions. Any valid code entry cancels the Fire activation.
20 Tamper
The Tamper function is continuously operational. When a Tamper zone is activated (1kΩ to 2kΩ), a tamper
alarm is generated; this requires to be reset by a code authorised for Tamper Reset - refer to option 51.7 =
PARAMETERS.Tamper Reset. If a tamper condition (open or short circuit) occurs, a tamper alarm is also
generated.
21 Bell Tamper
This function is identical to the operation of the Tamper function but is dedicated to bells, sirens and other
modules or output devices requiring tamper protection.
22 Beam Pair
This function is only operational when two consecutively addressed zones programmed as Beam Pair are
open in the set condition; the activation is identical to the Intruder function. The system cannot set if a single
Beam Pair is open.
NOTE: Beam Pair zones must be consecutively addressed; the first Beam Pair zone must have an even
number address, the second Beam Pair must have the next address (an odd number). For example,
valid Beam Pair addresses are 1036 & 1037, 2018 & 2031 - in this case, RIO 202 has not been
connected, therefore zone 2031 is the next address to 2018.
23 Battery Low
This function is used to monitor the voltage output of a standby battery connected to a power supply. The
activation (+) and de-activation (–) of Battery Low zones is recorded in the event log.
52 - Program Zones (cont'd)