51 - Parameters (cont'd)
35 = Fail to Set (Galaxy 60, 128, 500, 504 & 512)
This parameter determines the period of time that a zone must remain open, following the start of the setting
procedure, before the Fail Set outputs activate. The programmable range is 0–999 seconds; the default is
360 .
NOTE: The Fail to Set countdown time begins as soon as the setting procedure is started.
NOTE: The Fail to Set time should be approximately 5 seconds longer than the Exit Time (option 04), to
allow for the setting period of a set.
This parameter can be assigned a different value for each group.
36 = Battery Size (Galaxy 60, 128, 500, 504 & 512)
Enter the size of the standby battery on the Smart PSU that is connected to the Galaxy panel. The program-
mable range is 0–99Ah; the default is 0.
NOTE: The Battery Size (in Ahr's) should only be entered if a Smart PSU is being used to supply power
to the Galaxy panel.
37 = Standby Time (Galaxy 60, 128, 500, 504 & 512)
Enter the value (in hours) that the system is required to run on standby battery if there is a mains fail. The
programmable range is 0–99 hours; the default is 0.
NOTE: The Standby Time should only be entered if a Smart PSU is being used to supply power to the
Galaxy panel.
The Smart PSU calculates the battery run time from the programmed Battery Size (parameter 36) and the
load current. If the programmed Standby Time exceeds the calculated battery run time, a STANDBY
TIME LOW message is displayed on the keypad on attempting to exit engineer mode. Exiting engineer mode
is prevented until a Standby Time that is less than the calculated battery time is entered or a larger battery is
installed in the system and the new battery size is entered in the Battery Size parameter.
38 = ATM Delay (Galaxy 512)
This parameter determines the period of time before the selected ATM zone type is omitted following the
entry of one of the ATM codes (User 188–197). The programmable range is 0–30 minutes; the default
ATM Delay is 5.
39 = ATM Timeout (Galaxy 512)
This parameter determines the period of time that the selected ATM zone type is omitted following the entry
of one of the ATM codes (Users 188–197). The programmable range is 1–90 minutes; the default ATM
Timeout is 30.
Galaxy Programming Manual
60