Installing an Ethernet switch (modular) FN2012

5.16.3 Installing mounting kit FHA2029

144 | 354
Building Technologies
Fire Safety
The mounting kit (switch) is required to install Ethernet switch (modular) FN2012.
VdS does not allow the Ethernet switch to be installed in any other way. If the
stations do not provide enough room to install a mounting bracket, the Ethernet
switch must be installed in an empty housing. This empty housing must be
mounted below the station for conformity to VdS requirements.
Only one FN2012 may be mounted on a mounting bracket. The mounting brackets
are screwed onto the rear panel of the housing or, in the case of the
'housing (19", pedestal cabinet)', onto the side walls.
The mounting kit FHA2029 contains two mounting brackets:
Small mounting bracket
In the case of all wall-mounted empty housings, the installation position can be
on the right or on the left
In the case of stations in the Comfort housing, the installation position is on the
left
Large mounting bracket
In the case of stations in the Large housing, the installation position is on the
right
For FC2080 in 'housing (19", pedestal cabinet)'
Pack content
FHA2029 contains all the mechanical components required for installation in the
respective housing, including a cable kit comprising the following:
2x RJ45 Ethernet cable 1 m
1x RJ45 Ethernet cable 3 m
2-core signal cable, shielded, 1 m
Black cable AWG22, 1 m
1x blue and 1x red cable AWG18, 2 m
1x blue and 1x red cable AWG18, 3 m
View of mounting kit FHA2029
Figure 70: Mounting kit FHA2029, small and large mounting brackets