5.14 Network module (SAFEDLINK)

5.14.1 Installation

Building Technologies
Fire Safety
This component is installed in exactly the same way as for the operating units
with the PMI & mainboard FCM2004 and the PMI & mainboard FCM2027.
If you are installing only one network module (SAFEDLINK) FN2001-A1, you must
do so in the left-hand slot (X13).
When two network modules are used (SAFEDLINK) FN2001-A1, installation is
identical for both.
5
4
3
2
X13
Figure 60: Installation of both network modules (SAFEDLINK)
1
Network module (SAFEDLINK) on X13 (master module)
2
Fixing screws (2 pieces)
3
Mounting links on support plate
4
Nut for cable gland (2 per module)
5
Cable gland (2 per module)
6
Degraded mode network module (SAFEDLINK) on X12
7
Connector X1 on the rear of the network module
X3
Connection terminal FCnet
X13 Plug-type connection for main module
X12 Plug-type connection for degraded mode module
When using shielded cables, the cable screw connections are needed to secure
1
the shielding.
When installing only one network module (SAFEDLINK), ensure that the main
module is installed at the correct position on X13.
Mounting and installation of the compact control panels
Network module (SAFEDLINK)
X3
1
1
5
X3
6
X12