5.28.2.2 Connection of cable tree to periphery board
RT interface
Pin
Designation
1
Relay 1
2
Relay 2
3
Relay 3
4
Relay 4
5
Test
6
0 V supply
7
+ 24 V supply
8
Alarm
9
Alarm
10
Fault
11
--
12
Fault
13
K1
14
K1
15
K2
16
K2
17
K3
18
K3
19
K4
20
K4
Building Technologies
Fire Safety
Cable tree
Cable color
Cable no.
Black
1
Brown
1
Green
1
--
--
Gray/pink
1
Blue
1 (+ 2)
Red
1 (+ 2)
Gray
1 (+ 2)
Pink
1 (+ 2)
Violet
1 (+ 2)
Yellow
1 (+ 2)
White
1 (+ 2)
Black
2
Brown
2 + 3
Green
2
--
3
Gray/pink
2
--
3
--
--
--
3
Cable no.:
Cable 1 to periphery board, control cable VDE LI-CY 0.34 mm
560 mm, included in cable kit
Cable 2 to ↑ RT device, control cable 14-pin VDE LI-CY 0.34 mm
700 mm, included in cable kit
Cable 3 = loop made from wire jumpers 3 x 0.22 mm
Mounting and installation of the compact control panels
4 loop periphery board
Pin
Designation
X8-1
I/O1
X8-2
I/O2
X8-3
I/O3
--
--
X8-6
I/O6
X8-8
GND_01
X8-7
VSYS_01
X7-3
AL_NC
X7-2
AL_COM
X7-4
FAU_NO
X8-5
I/O5
X7-5
FAU_COM
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
5
RT interface [CH]
2 loops periphery board
Pin
Designation
X8-1
I/O1
X8-2
I/O2
X8-3
I/O3
--
--
X8-4
I/O4
X8-6
GND_01
X8-5
VSYS_01
X7-3
AL_NC
X7-2
AL_COM
X7-4
FAU_NO
X9-4
I/O8
X7-5
FAU_COM
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
, 14-pin, length
2
, length
2
x 40 mm
2
215 | 354
008851_s_en_--
2016-01-27

Hide quick links: