Mounting and installation FC2080
6
Installing the CPU card and communication card
6.11.2 Switching the network module with dual CPU operation
306 | 354
Building Technologies
Fire Safety
If a second CPU card is installed for redundant CPU operation, the network module
must be removed from the communication card and plugged into the second CPU
card, before it is installed, as shown.
1
Figure 167: Switching the network module from the communication card to the CPU card
1
Remove the network module from the communication card
2
Communication card
3
Plug the network module into the second CPU card
4
Second CPU card (optional)
2
3
4
008851_s_en_--
2016-01-27