Pin Assignments - Siemens FS20 Mounting & Installation

Fire detection system
Table of Contents

Advertisement

Mounting and installation of the compact control panels
5
Power supply (70 W)

5.6.2 Pin assignments

5.6.2.1 X1 mains connection
5.6.2.2 X2 Power supply and signal lines FP2001
96 | 354
Building Technologies
Fire Safety
Pin
Designation
1
2
N
3
L
Admissible cable cross-section: 0.2...2.5 mm²
Pin
Designation
8
Battery
7
Convert
6
Mains
5
Common GND
4
Usys +
3
Usys –
2
Akku +
1
Akku –
Admissible cable cross-section: 0.2...2.5 mm²
Battery
Convert
Main
Common GND
Usys +
+
Usys -
-
Akku +
F103
+
-
Akku -
F102
1 Cable tree to periphery board or fire terminal board
See also
2 X1 supply [➙ 75]
2 X1 supply [➙ 82]
2 X1 supply [➙ 90]
Description
Ground (protective conductor PE)
Neutral conductor
External conductor (L1)
Description
Detection line (#BATT): Battery fault
Detection line (#CONV): Power supply fault
Detection line (#MAINS): Mains fault
Ground (COMMON)
System supply (VSYS+)
System supply (VSYS-)
Battery supply (+)
Battery supply (–)
X2
#BATT
8
#CONV
7
6
#MAINS
COMMON
5
4
VSYS+
3
VSYS-
2
1
1
008851_s_en_--
2016-01-27

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents