Mounting and installation of the compact control panels
5
Redux module [DE]
5.23.2 Pin assignments
196 | 354
Building Technologies
Fire Safety
The pin assignment of the Redux module is listed in the manual of the Redux
module.
During connection please observe the following:
●
The data cables of the Redux module are connected to the RS485 interface.
●
The supply of the Redux module is connected to the periphery board.
–
Periphery board (2 loops) FCI2002-A1: Supply output 2 on plug X9
–
Periphery board (4 loops) FCI2004-A1: Supply output 1 on plug X8
●
The fault output of the Redux module can be connected to any I/O on the
periphery board. The I/O must be configured accordingly.
008851_s_en_--