Page 1
Introduction Safety notes Installing/mounting SITRANS F Connecting Ultrasonic Flowmeters SITRANS FS230 Commissioning Service and maintenance Compact Operating Instructions Technical specifications Dimension drawings Product documentation and support 7ME372 (HART/Modbus) 05/2021 A5E38755607-AC...
Page 2
Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
EDD: 1.04.00 tions support Modbus AMS Device Manager 12.0 or later FW: 1.04.00 SITRANS DTM V4.1 for gas Field communicator V3.8 FW: 1.03.00 for liquid HW: 002 and Device revi‐ sion 5 or later SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
• Do not use damaged or incomplete devices. Security information Siemens provides products and solutions with industrial security functions that support the secure operation of plants, systems, machines and networks. In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement –...
The content reflects the technical status at the time of publishing. Siemens reserves the right to make technical changes in the course of further development.
These include, for example: • National Electrical Code (NEC - NFPA 70) (USA) • Canadian Electrical Code (CEC) (Canada) Further provisions for hazardous area applications are for example: • IEC 60079-14 (international) • EN 60079-14 (EU) SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Note Operation under special ambient conditions We highly recommend that you contact your Siemens representative or our application department before you operate the device under special ambient conditions as can be encountered in nuclear power plants or when the device is used for research and development purposes.
• Observe the specifications for the electrical data on the certificate and/or in Technical specifications (Page 93). WARNING Dust layers above 5 mm Risk of explosion in hazardous areas. Device may overheat due to dust build up. • Remove dust layers in excess of 5 mm. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 14
WARNING Field wiring installation Risk of explosion in hazardous areas. May cause death or serious injury. Ensure that the national requirements of the country in which the devices are installed are met. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
3. The maximum dust layer shall be no greater than 5 mm (T5 85°C). 4. The SITRANS FST030 industrial enclosure shall be bonded to the sensor (e.g. the SITRANS FSS200) that is powered via the "SSL interface", M12 connector (Pins 1 to 4). SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Ensure that maximum permissible operating pressure of the device is not exceeded. Refer to the information on the nameplate and/or in Technical specifications (Page 93). SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
The device can overheat or materials become brittle due to UV exposure. • Protect the device from direct sunlight. • Make sure that the maximum permissible ambient temperature is not exceeded. Refer to the information in Technical specifications (Page 93). SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Cable connection between FST030 and Ports for I/O, Communications external DSL, up to 150 m ④ ⑨ Path 1-4 upstream (A) Ports for analog input or RTDs ⑤ ⑩ Path 1-4 downstream (B) Protective earth SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
1. Mount mounting bracket with cushion pad on pipe using fastening brackets/U-bolts and supplied pipe adaptor. Note U-bolts and other miscellaneous hardware are not supplied with the flowmeter. 2. Tighten nuts (torque: 10 Nm). SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
1. Remove lid lock screw of display cover. 2. Remove display cover. 3. Use a small screwdriver or blade to loosen the three retaining clips within the transmitter. 4. Carefully pull out local display. 5. Turn display into desired position. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Care must be taken when opening the lid to avoid the lid falling. Note Mounting screws are not included You will need four screws, able to support at least 25 kg (55 lbs). SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 24
Note Mounting on pipe or in panel For mounting on pipe or on a panel see the installation instructions for the "Pipe/panel mount kit" which are provided with the optional pipe/panel mount kit. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
1. Remove mounting bracket from DSL. 2. Mount bracket on a wall using four screws. Figure 3-2 Mounting bracket on wall 3. Mount DSL on mounting bracket using four screws. Figure 3-3 Mounting DSL to mounting bracket SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 26
2. Mount bracket on a horizontal or a vertical pipe using ordinary hose clips or duct straps. Figure 3-4 Mounting bracket on vertical pipe Figure 3-5 Mounting bracket on horizontal pipe Figure 3-6 Mounting bracket on big horizontal pipe 3. Mount DSL on mounting bracket using four screws. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
2. Using the supplied space bar, set the distance between the sensors according to the spacing index number provided by transmitter. The spacing index provides the correct distance between the sensors based on the pipe size given. Before continuing refer to the Reflect mount installation diagram example below. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
The device can be damaged, destroyed, or its functionality impaired through improper mounting. • Before installing ensure there is no visible damage to the device. • Mount the device using suitable tools. See operating instructions. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
• If the device contains hazardous media, it must be emptied prior to disassembly. Make sure that no environmentally hazardous media are released. • Secure the remaining connections so that no damage can result if the process is started unintentionally. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Damage to device through formation of condensation if the temperature difference between transportation or storage and the mounting location exceeds 20 °C (36 °F). • Before taking the device into operation, let the device adapt for several hours in the new environment. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 32
Exception: It may be permissible to omit connection of the equipotential bonding for devices with type of protection "Intrinsic safety Ex i". WARNING Unprotected cable ends Risk of explosion through unprotected cable ends in hazardous areas. • Protect unused cable ends in accordance with IEC/EN 60079-14. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 33
• Devices having the type of protection "Intrinsic safety Ex i" may also be connected in energized state in hazardous areas. WARNING Energized devices Risk of electric shock or explosion. When energized the device may be opened by qualified personnel only. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 34
• Ensure that the cover of the non-intrinsically safe circuits complies with degree of protection IP30 or higher according to IEC/EN 60529. • Separate connections of the non-intrinsically safe circuits in accordance with IEC/ EN 60079-14. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
3. Place F-connector tool around cable and slide up to engage F-connector nut. 4. Push cable through the gland opening. Ensure that the center lead is aligned with connector port in the transmitter. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
2. Apply the supplied grease to the internal threads at the large end of the thread connector. ⑥ ③ 3. Observing the upstream and downstream orientation , connect upstream sensor cable ⑤ from the transmitter port (1A) to the sensor and make connection snug. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
2. Apply Super Lube to the internal threads at the large end of the thread connector. ③ ④ 3. Observing the upstream and downstream orientation , connect upstream sensor cable from transmitter port (1A) and make connection snug. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 39
Path 1 - Upstream sensor cable to internal DSL port transmitter port (1B) (1A) ⑤ Hi Precision mounted sensors Figure 4-3 Hi Precision Reflect mount single enclosure wiring 5. Tighten all cable glands to obtain optimum sealing. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 40
2. Apply Super Lube to the internal threads at the large end of the thread connector. ③ ⑤ 3. Observing the upstream and downstream orientation , connect upstream sensor cable from transmitter port (1A) and make connection snug. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 41
Path 1 - Upstream sensor cable to internal DSL port (1A) Figure 4-4 HI Precision Direct mount Dual enclosure sensor wiring 5. Tighten all cable glands to obtain optimum sealing. 6. Refer to transmitter FST030 Operating Instructions to program transmitter. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
5. Finishing the DSL connection (Page 50) 4.5.1 Preparing for the external DSL connections 1. Remove lid from DSL 2. Remove F connector tool from DSL and use it to connect the sensor cables. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
4. Push cable through gland opening. Ensure that center lead is aligned with connector port in external DSL. 5. Tighten F-connector using tool until you meet mechanical stop. 6. Remove F-connector tool. 7. Mount and tighten cable gland. Repeat these steps for each sensor cable. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
For easier access unplug the terminal connector. After connecting the wires, plug the terminal connector back in. Note RTD shield grounding Make sure that the RTD cable shield is properly grounded. Consult the FSS200 Installation Manual on how to ground the RTD cable shield. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Connecting 4 to 20 mA current input cable (passive) Note Connection of optional devices The DSL provides the option of connecting two additional devices to channels 5 and 6. Do not connect two devices to one channel. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 46
1. Remove cap and ferrule from cable gland and slide onto cable. ① ② 2. Remove one of the blind plugs ( ) and fit cable gland. 3. Push cable through gland opening. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 47
Wire to Isource - (green) ⑦ ⑤ 5. Ground the RTD cable shield in the external DSL by sliding the crimp lug on wire onto ⑧ one of the installed strain reliefs screws SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
1. Connect DSL using the supplied 4-wire cable with M12 connectors to both the external DSL and the transmitter. Note Grounding The SSL cable shield is only mechanically connected to the grounding terminal (PE), when the M12 plug is correctly tightened. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 49
4. Push cable through gland opening. 5. Connect the four wires according to list below. Terminal connector Description Wire color +15 V DC Orange 0 V DC Yellow White Blue 6. Assemble and tighten cable gland. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
(bend cables downward) immediately before cable glands. Note Protection class The DSL is IP68 only if the lid is properly mounted and all M20 holes are closed with appropriate blind plugs or cable glands. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Current output/communication outputs (channel 1) 2. Remove lid lock screw for terminal connections lid. 3. Remove lid for terminal connections. A label showing the configuration is placed at the back of the terminal connections lid. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Configuration of channels 1, 2, 3 and 4 Figure 4-6 Configuration label 4.6.1.1 Terminal layout (industrial enclosure) The following table shows: • Which cable with which terminal • Hardware and software configuration of the channels SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
The wiring tool is located in the application terminal compartment. Figure 4-8 Wiring tool location 1. Insert wiring tool hook into receptor slot. 2. Press wiring tool wedge into top slot to spread clamp plates. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
2. Remove one of the blind plugs and fit cable gland. 3. Remove cap and ferrule from cable gland and slide onto cable. 4. Push cable through open gland; anchor cable with clamp bar. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Connecting 4.6 Connecting industrial enclosure 5. Connect wires to terminals according to list below. Terminal number Description Wire color (Siemens) 15 V Orange Yellow RS-485 / B White RS-485 / A Blue 6. Assemble and tighten cable gland 7. Remove O-ring from lid.
It is not required to use shielded cables for the pure 4 to 20 mA current output. Note HART communication It is recommended by the FieldComm Group (FCG) to use shielded cables for the HART communication. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 57
2. Push cable through open gland and cable path. 3. Restore ferrule and tighten cap to lightly hold cable in place. 4. Signal cable screen is folded back over outer sheath and grounded beneath cable clamp. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 58
Signal output: < 500 Ω at 14 to 24 VDC (active), 14 to 30 VDC (passive) Relay output: 30 VAC/VDC, 100 mA Passive signal input: 15 to 30 VDC, 2 to 15 mA SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
⑫ IO[3]+ (active) IO[3] (common) Functional Earth Functional Earth 4.6.6 Connecting the power supply 1. Open power supply terminal protection cover. 2. Remove cap and ferrule from cable gland and slide onto cable. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 60
AC connection DC connection Power: 100 to 240 V AC, 47 to 63 Hz Power: 20 to 27 V DC 6. Close and latch power supply terminal protection cover. 7. Tighten cable gland. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Wind lid further by one quarter of a turn to seal on the O-ring. 6. Reinstate and tighten lid lock screw. 7. Ensure that moisture does not penetrate the inside of electronics enclosure. Bend cables downward immediately before cable glands. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Input/output connection (channels 2 to 4) ③ Modbus connection 2. Loosen spring screws on enclosure lid. 3. Open enclosure lid. A nameplate showing the configuration is placed on the inside of the transmitter enclosure lid. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Updates (to be filled in on firmware and hardware updates) ⑦ Configuration of channels 1 to 6 Figure 4-10 Example configuration label See also Input/output configuration (Page 73) 4.7.1.1 Terminal layout (wall mount) 24 V DC or 110/230 V AC SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Connecting the sensor cables (internal DSL only) Preparing for the connection 1. Loosen the four lid screws. 2. Open the lid. 3. Remove F-connector tool from wall mount enclosure. Figure 4-12 F-connector tool location SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
7. Mount and tighten the cable gland. Repeat these steps for each sensor cable. 4.7.3 Connecting the SSL cable (wall mount enclosure) M12 connector version The SSL cable is provided with M12 style stainless steel plugs. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 66
Figure 4-13 Cable end 2. Remove cap and ferrule from cable gland and slide onto cable. ① 3. Remove blind plug and fit cable gland. Figure 4-14 Connection - SSL cable blind plugs SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 67
5. Remove cap and ferrule from cable gland and slide onto cable. 6. Push cable through open gland; anchor cable screen and wires with clamp bar. 7. Remove terminal block from DSL cassette. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 68
Connecting 4.7 Connecting wall mount enclosure 8. Connect wires to terminals according to list below. Terminal number Description Wire color (Siemens cable) 20 V Orange Yellow RS-485 / B White RS-485 / A Blue 9. Ensure the DIP switches are all set to OFF.
The terminal connector is detachable For easier access unplug the terminal connector. After connecting the wires, plug the terminal connector back in. – Wall mount transmitter Modbus ④ ⑤ 6. Tighten cable gland. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Procedure 1. Open enclosure lid. 2. Remove blind plug and fit cable gland. 3. Push cable through open gland and cable path. 4. Restore ferrule and tighten cap to hold cable in place. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Non-Ex versions can be connected as either active or passive. 4.7.6 Connecting channels 2 to 4 Channel 2 is for output only, channels 3 to 4 can be ordered as either inputs/outputs or relays, see Preparing wall mount enclosure connections (Page 62) SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 72
The numbers in the graphics below refer to table Preparing wall mount enclosure connections (Page 62) If connected as input or output (channels 2 to 4) Active configuration Passive configuration ⑫ ⑬ ⑪ ⑫ Termination example for channel 3 SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
ChXa+ • Alarm item Active • NAMUR status signals Output Current output Frequency output Passive Pulse output ChX- Status output ChXC • Alarm class ChX+ • Alarm item • NAMUR status signals Passive SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 74
Medium temperature ChXC • Viscosity • Density ChXa+ • Sensor temperature Active • Auxiliary temperature Current input Process values Passive • Pressure ChX- • Medium temperature ChXC • Viscosity • Density ChX+ Passive SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
2. Remove cap and ferrule from cable gland and slide onto cable. ④ ⑤ 3. Remove one of the blind plugs ( ) and fit cable gland. 4. Push cable through gland opening. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
• torque between 0.5 to 0.6 Nm • One wire per terminal connection 1. Open enclosure lid, unscrew power supply terminal protection cover screw, and remove protection cover. 2. Remove blind plug and fit cable gland. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 77
Connecting 4.7 Connecting wall mount enclosure 3. Push cable through open gland and cable path 4. Restore ferrule and tighten cap to lightly hold cable in place. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
4.7.9 Finishing the transmitter connection (wall mount) Connection check-up 1. Firmly tighten cable glands and insert blanking plugs in unused cable entries. 2. Check individual wire installation by tugging firmly. 3. Close lid. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 79
Connecting 4.7 Connecting wall mount enclosure 4. Tighten the four spring screws. 5. Ensure that moisture does not penetrate to inside of electronics enclosure. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
• Check prior to commissioning that the cover, cover locks, and cable inlets are assembled in accordance with the directives. Exception: Devices having the type of protection "Intrinsic safety Ex i" may also be opened in energized state in hazardous areas. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
The device is commissioned/operated with the buttons on the local display. The buttons are actuated by touching the glass panel on the appropriate button. The graphical display above the buttons gives a menu-guided operation of the individual device function/ SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 83
Automatic, display backlight goes off automatically 30 seconds after the last button press. Note Operation does not require opening of the device. This means that the high degree of protection of IP67 and safety in hazardous areas are guaranteed at all times. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
PIN codes can be changed in Security (5). Note Lost PIN code If the PIN code is lost, provide Siemens customer support with the transmitter serial number (see nameplate). Siemens customer support will provide a code to be entered in PIN recovery (5.4). Disable access level control If logged in as Expert you can Deactivate user PIN meaning that you will always be logged in as User and will not be prompted to enter the password.
Essential parameters should be considered before using the device for the first time. For any subsequent startup, after power-on, the device automatically starts in operation view. A transition screen showing first the Siemens logo and then the current firmware revision of the product is displayed while the first measurement is being processed.
Use of a computer in a hazardous area If the interface to the computer is used in the hazardous area, there is a risk of explosion. • Ensure that the atmosphere is explosion-free (hot work permit). SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
WARNING Impermissible repair of explosion protected devices Risk of explosion in hazardous areas • Repair must be carried out by Siemens authorized personnel only. WARNING Maintenance during continued operation in a hazardous area There is a risk of explosion when carrying out repairs and maintenance on the device in a hazardous area.
Page 89
• Before you open the enclosure or remove enclosure parts, de-energize the device. • If maintenance measures in an energized state are necessary, observe the particular precautionary measures. Have maintenance work carried out by qualified personnel. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
The on-board battery is used to maintain real time clock and should only be replaced with Panasonic BR1225A/BN. Siemens spare part number: A5E41372210 The battery is located in the transmitter cassette. The transmitter cassette location can be found in the exploded view.
Observe the specific reg‐ ulations valid in your country. Further information about devices containing batteries can be found at: Information about battery / product return (WEEE) (https:// support.industry.siemens.com/cs/document/109479891/) SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 92
Service and maintenance 6.5 Disposal SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Technical specifications Note Device specifications Siemens makes every attempt to ensure the accuracy of these specifications but reserves the right to change them at any time. Power Table 7-1 Power supply Description Specification Supply voltage • 100 to 240 V AC, 47 to 63 Hz •...
Fail-safe value • Current value Galvanic isolation • All inputs and outputs are galvanically isolated PELV circuits with 60 V DC isolation from each other and ground. Maximum test voltage: 500 V AC SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
• Fail-safe value • Current value Galvanic isolation All inputs and outputs are galvanically isolated PELV circuits with 60 V DC isolation from each other and ground. Maximum test voltage: 500 V AC SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 96
Channels 2 to 4 Pulse 41.6 µs to 5 s pulse duration Resolution 1 μs Frequency 0 to 10 kHz, 50 % duty cycle, 120 % overscale provision Resolution 0.2 Hz Load < 750 Ω SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
14.9 mH • Group IIC • 17.8 μH/Ω • 18.0 μH/Ω • • Groups IIB, III • 71.2 μH/Ω • 72.2 μH/Ω • • Group IIA • 142 μH/Ω • 144 μH/Ω • SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Page 98
28 V DC 4.2 V DC 28 V DC 28 V DC 28 V DC 85 mA 118 mA 87 mA 87 mA 87 mA 584.5 mW 124 mW 601 mW 601 mW 601 mW SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
SSL (power & signal) Analog input I/O 5 Analog input I/O 6 17.42 V DC 30 V DC 459 mA 100 mA 2.0 W 0.75 W 2.52 nF 0 nF 315 nH 105 nH SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Technical specifications 7.8 Construction Table 7-17 Siemens SSL cable capacity SSL cables 264.6 pF/m 1.12 µH/m Table 7-18 Output parameters RTD 5, RTD 6 (any combination of con‐ Sensor outputs, each nections) (up to 8) 4.52 V DC 17.43 V DC 13.8 mA...
Page 101
Material Aluminum with corrosion-resistant coating Ingress protection IP66/67/NEMA 4X to EN/IEC 60529 (1 meter for 30 min) Mechanical load 18 to 1000 Hz random, 3.17 g RMS, in all directions, to EN/IEC 68-2-36 SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
Cable glands and fittings for use in Explosive Atmospheres 1. M20 to ½ NPT adaptors, M12 connector and plugs supplied by Siemens have been approved as part of the certification. 2. Cable glands shall be rated for a minimum ingress protection rating of IP54 and have an ambient temperature rating suitable for the installation with a safety factor of 5 °K above the...
• CSAE 21UKEX1109X • IECEx SIR 11.0150X EAC Ex 1Ex d e ia [ia Ga] IIC T6 Gb Ex tb [ia Da] IIIC T85°C Db Ambient temperature range Ta = -40°C to 60°C SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
-40 to +85 °C (-40 to 185 °F) Storage: -40 to +100 °C (-40 to 212 °F) Note SensorFlash functions support Only the supplied 4 GB SD cards are supported for backup, restore, logging, and firmware update. SITRANS FS230 Compact Operating Instructions, 05/2021, A5E38755607-AC...
– "Download as html5, only PC": Open or save the manual in the HTML5 view on your PC You can also find manuals with the Mobile app at Industry Online Support (https:// support.industry.siemens.com/cs/ww/en/sc/2067). Download the app to your mobile device and scan the device QR code. Product documentation by serial number Using the PIA Life Cycle Portal, you can access the serial number-specific product information including technical specifications, spare parts, calibration data, or factory certificates.
Additional information on our technical support can be found at Technical Support (http:// www.siemens.com/automation/csi/service). Service & support on the Internet In addition to our technical support, Siemens offers comprehensive online services at Service & Support (http://www.siemens.com/automation/service&support). Contact If you have further questions about the device, contact your local Siemens representative at Personal Contact (http://www.automation.siemens.com/partner).