Installing The Fiber Optic Cable Network Module; Replacing The Din Rail Clip - Siemens FS20 Mounting & Installation

Fire detection system
Table of Contents

Advertisement

Mounting and installation of the compact control panels
5

Installing the fiber optic cable network module

5.15 Installing the fiber optic cable network module

5.15.1 Replacing the DIN rail clip

134 | 354
Building Technologies
Fire Safety
The identical fiber optic cable network modules FN2006-A1 and FN2007-A1 can be
installed on a DIN rail either horizontally or vertically. If the DIN rail clip is removed,
horizontal installation on the flanges is also possible.
The diagram below shows how to install or replace the DIN rail clip for the
installation variants.
6
5
4
Figure 63: View of the DIN rail clip installation variants
1
Fixing screws for DIN rail clip
2
Mounting holes for DIN rail clip on the front side
3
Lower flanges for installation on the rear panel
4
DIN rail clip
5
Fiber optic cable network module on the rear side
6
Upper flange for installation on the rear panel
Replacing the DIN rail clip
1. Loosen the two countersunk screws (1) and remove the DIN rail clip (4).
2. Fasten the DIN rail clip (4), rotated by 90º, at the threaded holes (2) using both
countersunk screws (1).
1
3
2
008851_s_en_--
2016-01-27