Cable Kit (Communication) - Siemens FS20 Mounting & Installation

Fire detection system
Table of Contents

Advertisement

Mounting and installation of the compact control panels
5

Cable kit (communication)

5.29 Cable kit (communication)
216 | 354
Building Technologies
Fire Safety
The cable kit (communication) FCA2014-A1 is used as an intermediate piece for
wiring the external lines to the modules on the operating unit. The connecting
cables supplied are fully assembled and have a length of 1110 mm. The cable kit is
mounted in the top right of the housing instead of the shield connection terminal
blocks.
Figure 115: Installation of the cable kit (communication) on the rear panel (example, Standard housing)
1
Screw bushings in rear panel for terminal strip
2
Terminal strip with 2 shield connection terminal blocks and connection
terminals
3
2x fixing screws
4
Periphery board
Mounting steps
1. First remove the shield connection terminal blocks if present.
2. Screw the mounting rail (2) to the screw bushings in the rear panel (1) using
the two fixing screws (3).
3. Now wire the existing module to the operating unit using the cables provided
according to the allocation plan of the respective module.
4. Guide the cable to the operating unit along the rear panel and fasten using
cable ties.
1
2
3
4
008851_s_en_--