6.4.3 Adjustment elements

6.4.3.1 Address switch, S201
78 | 248
Building Technologies
Fire Safety
Diagram showing how to calculate the maximum cable length
2
Number of optional participants
With the address switch S201, the binary address (1...16) of the extinguishing
terminal is set and the 3rd source of voltage is switched on.
The address switches are preset as follows:
XCM2002 exting. terminal (1 sector) = address 1
XCM2003 exting. terminal (4 sectors) = each address 1
XT2001 exting. terminal (remote) = address 2
Switch pos.
Designation
S201.1
ADDR1
S201.2
ADDR2
S201.3
ADDR3
S201.4
3SRC-OFF
1
0
1
2
2x1.5mm2, 24? /km (back&forward)
(red)
(blue)
2x0.75mm2, 34? /km (back&forward)
2x0.8ø (2x0.5mm2), 70? /km (back&forward)
(green)
(violet)
2x0.6ø (2x0.28mm2), 125? /km (back&forward)
3
Function
Address bit 1
Address bit 2
Address bit 3
3rd source ON (default)
S201
ON
3
4
ADDR
1 2 3
4
5
A6V10210390_m_en_--