Alarms and alerts

Transient alarms

Alarm event priorities

Info Only and None event priority

Alarm indicators

7EN05-0390-00
Related Topics
Configuring digital input alarms using ION Setup
Configuring onboard digital inputs using ION Setup
These alarms are triggered by voltage transient activity (i.e., ITI CBEMA Type 1
disturbances).
You must configure nominal voltage for these alarms to function.
The Threshold setup register in the Transient module defines what voltage
disturbance magnitude should be considered as transient activity. Threshold is
interpreted as a percentage of the nominal system voltage, plus 100. For example,
if you want transients recorded when voltage deviates from nominal by 20%, enter
120 into the Threshold setup register.
For more information on the Transient module, download the ION Reference at
www.usa.siemens.com/pds.
Related Topics
Transient overview
Your meter's alarm priorities correspond to event priority ranges.
Alarm priority
High (red)
Medium (yellow)
Low (blue)
Info Only (no alarm)
1
None (no alarm or event)
1
1
Alarms with priority of Info Only or None are not indicated or displayed.
Alarms with a priority of Info Only or None are not shown on the meter's display,
and do not function as alarms. If the alarm's priority is set to Info Only, and the
event priority is greater than the event log cutoff value, the associated event is
recorded in the meter's event log. If the alarm's priority is set to None, the event
priority is automatically set to zero, and no associated event is logged in the
meter's event log.
For events that you want to log for future reference or troubleshooting, but don't
want alarm functions, set the alarm priority to Info Only.
For nuisance events that frequently occur and you have no desire to log for
reference or troubleshooting, set the alarm priority to None.
Related Topics
Event log overview
Your meter's display has an alarm indicator to show you what alarm levels have
been detected (active or historic) and whether they have been acknowledged.
Event priority
192 - 255
128 - 191
64 - 127
1 - 63
0
125