Fault Messages On The Person Machine Interface; Fault Indicators On Components - Siemens FS720 Commissioning, Maintenance, Troubleshooting

Fire detection system
Table of Contents

Advertisement

24.3
LED
LED flashes
1
FAULT
5
System Fault
8
Remote alarm Fault /
Off
10
Alarm device Fault /
Off
12
Control function Fault /
Off
24.4
Building Technologies
Fire Safety

Fault messages on the Person Machine Interface

1
8
10
5
12
Fault messages on the Person Machine Interface
The table below shows the causes and measures should a fault be displayed.
Cause
The 'Site' has a fault
Failure of the main CPU
'Fault of a component
Communication fault of a
networked 'Station'
Transmission equipment has a
'Fault'
'Acoustic control line 'Fault'
'Fire control line 'Fault'

Fault indicators on components

The components are equipped with LED indicating the status of the component.
You will find the meaning of the indications in document A6V10210368. See
chapter 'Applicable documents'.
See also
Applicable documents [
Fault messages on the Person Machine Interface
What must be done
Check whether another fault LED is flashing,
if not:
Check the display
Check whether the 'Fault' control input is
activated
Visual check of the cable connections
Check whether the red LED H37 on the
operating unit FCM72xx is on:
Exchange PMI & mainboard
'Restart 'Station'
When the 'Fault' is still indicated:
exchange the module
Check the transmission line
Check the faulty 'Station'
Check remote transmission
'Check the 'Line' for open line/short-circuit or
end-of-line element (EOL) is missing or
defective
'Check the 'Line' for open line/short-circuit
Check the function of the external control
devices
Check the function, any existing feedback
switch
8]
Repair
24
109
A6V10210416_f_en_--
14.01.2013

Advertisement

Table of Contents
loading