ANN-BUS Devices

ANN-I/O Board Layout

Figure 2.20 illustrates the ANN-I/O board showing locations of screw terminals for connection to
the FACP, pin connectors for connecting LEDs and the DIP switch for selecting the ANN-BUS ID
number.

Specifications

Max. ANN-BUS Voltage: 28 VDC
Max. Current:
Alarm: 200 mA
Standby: 35 mA
Each LED: 10 mA
Operating Temperature: 32
For indoor use in a dry location only
MRP-2001 Series Manual — P/N 53040:H 1/26/2017
Terminals not used (future)
ANN-BUS Connector
Figure 2.20 ANN-I/O Board Layout
o
o
o
o
F to 120
F (0
C to 49
C)
Installation
ANN-BUS (ID#)
Address DIP
switch
43