Commissioning Steps; Commissioning V/F Control - Siemens Sinamics G120 CU240E Operating Instructions Manual

Table of Contents

Advertisement

Commissioning
4.6 Commissioning with the operator panel
4.6.4

Commissioning steps

The following section provides a step-by-step guide to quick commissioning, which is
sufficient for the majority of applications.
The first step in commissioning a drive train is to ensure that the converter and motor are
harmonized. This converter-motor combination can then be adapted in line with the
requirements of the drive machine
The frequency inverter is adapted to the requirements of an application by parameterizing it.
A corresponding parameter list with explanations is provided on the following pages.
4.6.5

Commissioning V/f control

Since the load characteristic can be set as required, V/f control is sufficient for many drive
trains. A drive train that operates with
entering the following parameters.
Parameter settings for V/f control
Table 4- 5
Parameter
P0003 = 1
P0010 = 1
Table 4- 6
Parameter
P0100 = 0
P0230 = 0
P0233 = ...
P0234 = ...
74
Setting the access level and parameter filter
Description
User access level
1: Standard: Allows access to the most frequently used parameters (factory setting)
2: Extended: Allows extended access, e.g. to inverter I/O functions
3: Expert: For experts only
Commissioning parameter filter
0: Ready (factory setting)
1: Quick commissioning
30: Factory setting
To parameterize the motor rating plate data, set P0010 = 1.
Data on the environmental conditions at the installation location
Description
Europe / North America (line frequency of region)
0: Europe [kW], standard frequency 50 Hz (factory setting)
1: North America [hp], standard frequency: 60 Hz
2: North America [kW], standard frequency: 60 Hz
Shows the selected output filter
0: No filter (factory setting)
Filter inductance of the output filter used
0.000 (factory setting)
Filter capacitance of the output filter used
0.000 (factory setting)
V/f control with a linear characteristic
Operating Instructions, 08.10. 2008, t.b.d.