Table 5- 28
Parameter
P0003 = 2
P0400 = ...
P0408 = ...
P0410 = ...
P0491 = ...
P0492 = ...
P0494 = ...
P1442 = ...
P1300 = 21
or
P1300 = 23
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
The most important speed encoder parameters
Description
Extended access to the inverter functions
Encoder type
0: Encoder signal is not evaluated
•
2: Encoder with pulse tracks A and B without zero pulse
•
12: Encoder with pulse tracks A, B and zero pulse
•
Encoder pulses per revolution
Inverts the encoder signal
0: The encoder signal is not influenced
•
1: The encoder signal is inverted
•
Response when the speed signal is lost
0: Motor is shut down with fault message F0090
•
1: Alarm and switch to SLVC, if in SVC
•
Permissible speed difference for monitoring the encoder signal (F0090)
Delayed response when the speed signal is lost
Filter time for the speed encoder actual value
Control type: Vector control with speed encoder
Functions
5.7 Closed-loop control
117