Siemens Sinamics G120 CU240E Operating Instructions Manual page 187

Table of Contents

Advertisement

Bit
Value
Meaning
13
1
--
0
Motor overload
14
1
Clockwise rotation
0
Counter-clockwise rotation
15
1
--
0
Converter overload
Status word 2 (ZSW2)
Status word 2 has the following default assignment. This can be changed by means of BICO.
Table 5- 68
Default setting for status word 2 (not defined for VIK/NAMUR)
Bit
Value
Meaning
0
1
DC brake active
1
1
n_act < P2167
2
1
n_act ≧ P1080
3
1
i_act ≧ P2170
4
1
n_act > P2155
5
1
n_act ≦ P2155
6
1
Speed setpoint reached
7
1
DC link voltage < P2172
8
1
DC link voltage ≧ P2172
9
1
Speed ramp ended
10
1
Technology controller output ≦ P2292
11
1
Technology controller output > P2291
12
1
Vdc_max controller
13
1
Kinetic buffering and flexible response
14
1
Not used
15
1
Not used
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
Comments
Motor data displays overload status.
--
--
--
--
E.g. current or temperature
Description
DC brake active
Converter frequency < shutdown limit
Actual frequency > minimum frequency
Current ≥ limit value
Actual frequency > reference frequency
Actual frequency < reference frequency
Actual frequency ≥ setpoint
Voltage < threshold value
Voltage > threshold value
--
PI frequency < threshold value
PI saturation
--
--
--
--
5.11 Operation in fieldbus systems
Functions
187