Function check, "Safe Stop 1" (SS1)
This check involves the following steps:
Table 5- 74
No.
1.
2.
3.
4.
5.
6.
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
Description
Check the following points:
No safety fault
r9772.0 = r9772.1 = 0 (STO deselected and inactive), r9772.14 = 0
Check whether the motor involved is running. If yes, check the following
points:
That the cabling between the Control Unit and Power Module is correct
Correct assignment, drive No. - frequency inverter - Power Module - motor
That the hardware is operating correctly
That the shutdown paths are correctly wired
Correct STO terminal assignment at the Control Unit
Correct parameterization of the STO function
Routine for the forced checking procedure of the shutdown paths
Function, "Safe Stop 1" (SS1)
Description
Initial state
The frequency inverter signals "ready for switching on" (P0010 = 0)
No safety faults and alarms
r9772.0 = r9772.1 = 0 (STO deselected and inactive)
r9772.2 = r9772.3 = 0 (SS1 deselected and inactive)
Switch on the motor
Check whether the motor involved rotates
Select SS1 while the ON command is being issued
Check the following points:
The motor speed decelerates corresponding to the selected ramp time (if
required, use a stopwatch)
The motor coasts down to a standstill after the parameterized minimum
speed has been fallen below
The motor is braked and held by the mechanical brake if a brake is being
used
No safety fault
r9772.1 = 1 (STO active)
r9772.2 = 1 (SS1 selected)
r9772.14 = 1, if the monitoring function of the safety-relevant brake is
activated
Cancel SS1
Functions
5.12 Safety-related applications
Status
Status
209