3.3.1
Dimensions, hole drilling templates, minimum clearances, tightening torques
Overview of dimensions and hole drilling templates for the Power Modules
0.37 kW ... 1.5 kW
Retaining type
2 x M4 bolts
•
2 x M4 nuts
•
2 x M4 washers
•
Tightening torques
2.5 Nm (22.1 lbf.in)
•
Distances from other devices
Lateral: 30 mm (1.18 inch)
•
Top/bottom: 100 mm (3.93 inch)
•
Depth
Standalone: 145 mm (5.71 inch)
•
With CU240E: 187 mm (7.36 inch)
•
With CU240S: 208 mm (8.19 inch)
•
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
2,2 kW ... 4 kW
Retaining type
4 x M4 bolts
•
4 x M4 nuts
•
4 x M4 washers
•
Tightening torques
2.5 Nm (22.1 lbf.in)
•
Distances from other devices
Lateral: 40 mm (1.57 inch)
•
Top/bottom: 100 mm (3.93 inch)
•
Depth
Standalone: 165 mm (6.50 inch)
•
With CU240E: 207 mm (8.15 inch)
•
With CU240S: 228 mm (8.98 inch)
•
3.3 Mounting Power Modules
7,5 kW ... 15 kW
Retaining type
4 x M5 bolts
•
4 x M5 nuts
•
4 x M5 washers
•
Tightening torques
2.5 Nm (22.1 lbf.in)
•
Distances from other devices
Lateral: 50 mm (1.96 inch)
•
Top/bottom: 125 mm (4.92 inch)
•
Depth
Standalone: 185 mm (7.28 inch)
•
With CU240E: 227 mm (8.94 inch)
•
With CU240S: 248 mm (9.76 inch)
•
Connection
31