Acceptance Test And Report - Siemens Sinamics G120 CU240E Operating Instructions Manual

Table of Contents

Advertisement

Functions
5.12 Safety-related applications
5.12.5

Acceptance test and report

Acceptance test report for safety functions
To verify safety-related parameters, an acceptance test must be performed after initial
commissioning has been carried out and after the safety-related parameters have been
changed. The acceptance test must be documented in the form of a report. The acceptance
test reports are part of the machine documentation and must be archived accordingly.
The checksums (r9798 and r9898) ensure that subsequent changes to safety-related
parameters can be identified.
What must be carried out when an acceptance test is performed for safety functions?
1. Machine documentation
2. Function test
3. Complete the report
4. Enclosures with the report
206
Document the machine, including its fail-safe functions.
– Description of the machine and overview/block diagram
– Fail-safe functions for each drive
– Description of the fail-safe equipment
An empty document is provided as an example following this section.
Check each individual fail-safe function. An empty document is provided as an example
following this section.
Document the commissioning period and sign the report.
– Check the parameters for fail-safe functions.
– Document the checksums.
– Provide evidence showing that the data has been backed up and archived.
– Sign the report.
An empty document is provided as an example following this section.
Include records and printouts of measurements associated with the function test.
– Alarm reports
– Printouts of curve characteristics
– When required, you can create a list with all of the changed parameters of the
frequency inverter. Instructions on how to do this are available here:
http://support.automation.siemens.com/WW/view/de/29319456