Siemens Sinamics G120 CU240E Operating Instructions Manual page 39

Table of Contents

Advertisement

Avoiding electromagnetic disturbances
The frequency inverters are designed for operation in industrial environments where high
values of electromagnetic noise and disturbances are expected. Generally, correct
installation guarantees safe, reliable and disturbance-free operation. If difficulties do arise,
then please note the following guidelines.
Required measures
● Ensure that all of the devices in the cabinet are well-grounded using short grounding
● Ensure that every control device (e.g. a PLC) connected to the frequency inverter is
● Connect the return ground of the motors, which are controlled from the frequency
● Flat cables are preferred as they have a lower impedance at higher frequencies.
● The cable ends must be cleanly terminated and it must be ensured that unshielded
● The control cables must be routed separately from the supply cables. Power and control
● If at all possible, use shielded cables to connect the control circuit.
● Ensure that the contactors in the cabinet have the necessary interference suppression
● Use shielded cables for the motor connections, and ground the shielding at both ends
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
cables with high cross-sections, connected to a common grounding point or a grounding
bar.
connected to the same ground or the same grounding point as the frequency inverter
through a short cable with a large cross-section.
inverters, directly at the ground connection (PE) of the associated frequency inverter.
cables are as short as possible.
cables should cross at a 90° angle.
components; either using an RC circuit for AC contactors or using "free-wheeling diodes"
for DC contactors, whereby the noise suppression elements should be connected at the
coils. Varistor suppressors are also effective. This is important if the contactors are
controlled from the frequency inverter relay.
using cable clamps.
Connection
3.3 Mounting Power Modules
39

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120 cu240s pn-fSinamics g120 cu240s dpSinamics g120 cu240s pnSinamics g120 cu240sSinamics g120 cu240s dp-f

Table of Contents