Functions
5.11 Operation in fieldbus systems
Status word 1 (ZSW1)
Status word 1 (bits 0 to 10 in accordance with PROFIdrive profile and VIK/NAMUR, bits 11 to
15 for SINAMICS G120 only).
Table 5- 67
Bit assignments for status word 1 (for all PROFIdrive and VIK/NAMUR message frames)
Bit
Value
Meaning
0
1
Ready for switching on
0
Not ready for switching on
1
1
Ready for operation
0
Not ready for operation
2
1
Operation enabled
0
Operation disabled
3
1
Fault present
0
No fault
4
1
"Coast to standstill" not activated
0
"Coast to standstill" activated
5
1
"Quick stop" not activated
0
Quick stop activated
6
1
Switch-on disabled
0
Switch-on not disabled
7
1
Alarm present
0
No alarm
8
1
Speed deviation within tolerance
range
0
Speed deviation outside of tolerance
range
9
1
Master control requested
0
No control requested
10
1
Maximum frequency reached or
exceeded
0
Maximum frequency not reached
11
1
--
0
Alarm: Motor current/torque limit
reached
12
1
Motor holding brake active
0
--
186
Comments
Power supply switched on; electronics initialized; pulses disabled.
--
Converter is switched on (ON command present), no active fault,
converter can start as soon as "enable operation" command is
issued. See control word 1, bit 0.
--
Drive follows setpoint. See control word 1, bit 3.
--
Drive is faulty. The drive is faulty, which means that it is not in
operation and switches to "starting inhibit" mode once the fault has
been successfully rectified and acknowledged.
--
--
"Coast to standstill" (OFF 2) command present.
--
"Quick stop" (OFF 3) command present.
The drive only switches to the ON state when the "No coast down"
AND "No quick stop" commands (followed by "ON") are issued.
--
Drive still in operation; alarm in service/maintenance parameter; no
acknowledgement; see alarm parameter r2110.
No alarm is present or the alarm has disappeared.
Setpoint/actual value deviation within tolerance range.
--
The automation system is requested to assume control.
The master is not currently the master controller.
Converter output frequency is greater than or equal to the maximum
frequency.
--
--
--
Signal can be used to control a holding brake.
--
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.