5.5.6.5

General Steps for Commissioning Fail-Safe Functions

Description
The parameters designated with an "*" offer more setting possibilities than are listed here.
Refer to the parameter list for additional setting possibilities.
The following steps must always be carried-out when changing fail-safe functions:
Parameter
Description
P0003 = 3
User access level*
3: Expert: For expert use only
P0010 = 95 Commissioning parameter*
95: Commissioning the fail-safe functions
P9761
SI input password
If the password is entered correctly, access will be granted. If not, the
parameters for fail-safe functions are non-accessible and the user will
have to exit the commissioning mode for fail-safe functions manually
by using parameter P3900 = 11 which cancels all previous changes to
the parameters for fail-safe functions.
Change requested fail-safe parameters, then finish the parameterization with the following steps:
P9799
Checksum for SI parameters
Checksum of the fail-safe function parameters.
Enter value of r9798
P9899
Checksum for SI parameters
Checksum of the fail-safe function parameters.
Enter value of r9898
P3900 = 10 End of the safety commissioning*
10: Accept changes of fail-safe function parameters
11: Cancel changes of fail-safe function parameters
Control Units CU240S
Operating Instructions, 07/2008 - FW 3.2, A5E00766042B AD
Commissioning
5.5 Commissioning using the BOP
Unit
Default
Min.
1
0
0
0
-
12345
1000
-
000h
000h
-
000h
000h
0
0
Max.
4
95
99999
FFFFh
FFFFh
11
83