Functions
5.4 Setpoint sources
5.4.5

Running the motor in jog mode (JOG function)

Run motor in jog mode [JOG function]
The JOG function enables you to carry out the following:
● Test the motor and converter after commissioning to ensure that they function properly
● Move a motor or motor load to a specific position
● Run a motor (e.g. following program interruption)
This function allows the motor to start up or rotate with a specific jog frequency. This function
can normally be activated via the JOG button on the Basic Operator Panel,
When this function is enabled, the motor starts up ("ready for operation" status) when the
JOG button is pressed and rotates at the set JOG frequency. When the button is released,
the motor stops. This button has no effect when the motor is already running.
Parameter
P0003 = 2
P1057 = 1
P1058 = 5
P1059 = 5
P1060 = 10
P1061 = 10
100
(the first traverse movement, direction of rotation etc.)
Description
User access level
2: Advanced mode
JOG enable
0: JOG function disabled
1: JOG function enabled (factory setting)
JOG frequency CW
0 Hz ... 650 Hz in JOG mode of motor in clockwise direction of rotation;
5 Hz (factory setting)
JOG frequency CCW
0 Hz ... 650 Hz in the motor JOG mode in the counter-clockwise direction;
5 Hz (factory setting)
JOG ramp-up time
0 s ... 650 s / 10 s (factory setting)
Ramp-up time (in seconds) from 0 to
maximum frequency (P1082). The
ramp-up procedure in JOG mode is
limited by P1058 or P1059.
JOG ramp-down
0 s ... 650 s / 10 s (factory setting)
The ramp-down time (in seconds) from
the maximum frequency (P1082) to 0.
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.