Introduction
1.2 Adapting the frequency inverter to the particular application (parameter assignment for entry-level
personnel)
1.2.3

Parameters with follow-on parameterization

Parameters with follow-on parameterization
When you change certain parameters, the system may automatically change other
parameters accordingly. This makes it much easier to parameterize complex functions.
Example: Parameter P0700 (command source)
Parameter P0700 can be used to switch the command source from the fieldbus to digital
inputs. When the value of P0700 is changed from 6 (command source "fieldbus") to 2
(command source "digital inputs"), other parameter values are changed automatically:
● New functions are assigned to the digital inputs (P0701 ... P0713)
● New functions are assigned to the digital outputs (P0731 ... P0733)
● Inverter control is interconnected with the signals from the digital inputs (P0800, P0801,
For more information about follow-on parameterization for P0700, see the List Manual.