Technical data

8.1

Technical data of the CU240S

Technical data of the CU240S, CU240S DP, CU240S DP-F, CU240S PN and CU240S PN-F
Feature
Operating voltage
Heat loss
Setpoint resolution
Digital inputs
(dependent on the CU
type)
Analog inputs
Digital outputs
Analog outputs
Fail-safe inputs
(dependent on the CU
type)
PFH
Dimensions (WxHxD)
Weight
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
Data
Supply from the Power Module or an external 24 V DC supply
(20.4 V to 28.8 V, 0.5 A) via control terminals 31 and 32
< 40W
0.01 Hz
6 or 9, floating; PNP
Low < 5 V, High > 10 V, maximum input voltage 30 V, 5.5 mA
2, with 10-bit resolution
AI0: 0 V to 10 V, 0 mA to 20 mA and -10 V to+10 V
AI1: 0 V to 10 V and 0 mA to 20 mA
Both analog inputs can also be configured as digital inputs
3 relay outputs, 30 V DC / max. 0.5 A for a resistive load
2
AO0: 0 V to 10 V or 0 mA to 20 mA
AO1: 0 mA to 20 mA
2, two-channel, maximum input voltage 30 V, 5.5 mA
5 × 10E-8
Valid for all safety functions STO, SS1, SLS and SBC
73 mm x 178 mm x 55 mm
0.52 kg
8
223