Siemens Sinamics G120 CU240E Operating Instructions Manual page 137

Table of Contents

Advertisement

Table 5- 38
Parameter
P0003 = 2
P1215 = ...
P0731= 52.C
P0346 = ...
P1080 = ...
P1216 = ...
P1217 = ...
P1227 = ...
r0052.12
Opening the motor holding brake via P1218
Using parameter P1218, you can force the brake to open, e.g. in order to be able to
manually move a conveyor drive.
P1218 is ignored if the motor holding brake is closed because of an STO.
Secure loads held by the brake!
Since this procedure cancels the "Brake active" signal which, in turn, causes the brake to
be forced open, the user must ensure that, even when the motor has been powered-down,
all loads held by the brake are secured before the signal is canceled.
Table 5- 39
Parameter
P0003 = 3
P1218 = 1
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
Control logic parameters of the motor holding brake
Description
Enables extended parameter access
Enable motor holding brake
0 Motor holding brake disabled (factory setting)
1 Motor holding brake enabled
BI: Function digital output 1
Note:
To control the braking relay via the digital output, the following must apply for digital
output 1: P0731 = 52.C = 52.12
Magnetizing time time
0 ... 20 s, factory setting 1 s
Minimum frequency
0 ... 650 Hz, (0 Hz factory setting): minimum motor frequency, regardless of
frequency setpoint
Delay time for opening the brake
0 ... 20 s, factory setting 0.1 s
Note: P1216> brake release time + relay opening time
Holding time after runout
0 ... 20 s, factory setting 0.1 s
Note: P1217> brake closing time + relay closing time
Zero value detection monitoring time
0 ... 300 s, factory setting 4 s
"Brake active" status
WARNING
Parameter to force open a motor holding brake
Description
Enables expert access to parameters
Forcibly opens the motor holding brake
Functions
5.10 Technological functions
137

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g120 cu240s pn-fSinamics g120 cu240s dpSinamics g120 cu240s pnSinamics g120 cu240sSinamics g120 cu240s dp-f

Table of Contents