8.7

Common technical data, PM260 Power Modules

PM260
Feature
Line operating voltage
Input frequency
Power factor λ
Overload capability
Pulse frequency
Braking methods
Degree of protection
Operating temperature
Bearing temperature
Relative humidity
Installation altitude
Standards
Frequency inverter
Operating Instructions, 08.10. 2008, t.b.d.
8.7 Common technical data, PM260 Power Modules
Version
3 AC 660 V ... 690 V ± 10%
The power units can also be operated with a minimum voltage of 500 V –
10 %. In this case, the power is linearly reduced as required.
47 Hz ... 63 Hz
0.95
The Power Module PM260 can either be operated with high overload
(HO) or low overload (LO). In order to avoid overtemperature of the
Power Module, after the overload, as a minimum its load must decrease
back to the base load (HO base load or LO base load).
HO base load
7.5 kW ... 37 kW
LO base load
11 kW ... 55 kW
16 kHz
Regenerative energy
IP20
HO base load
-10 °C ... +50 °C (14 °F ... 122 °F)
LO base load
-10 °C ... +40 °C (14 °F ... 104 °F)
-40 °C ... +70 °C (-40 °F ... 158 °F)
< 95% RH - condensation not permissible
Up to 1000 m (3300 ft) above sea level
CE
Technical data
The permissible operating voltage
depends on the installation altitude
150% overload for 57 s
200% overload for 3 s
100% HO base load for 240 s
110% overload for 57 s
140% overload for 3 s
100% LO base load for 240 s
Higher operating temperatures
are possible when the rated
power is reduced
Higher altitudes are possible
when the rated power is
reduced