Chapter 6 Schlage Adaptable AD-300 Series Locks

Addressing the AD-300 Lock

The AD-300 lock is addressed using the Schlage Utility Software (SUS), which is run from the Pideon PDA. The
address used by the AD-300 locks go from 0 to 15.
addressing an AD-300 lock it is important to remember this. An address of 0 for the AD-300 lock equals an
lite blue
address of 1 in
The AD-300 lock is directly connected to the lite blue controller at RS485-1 then the address of the
Example:
AD-300 lock should be set to 1. If the AD-300 is connected to RS485-1 but daisy chained to another compatible
RS-485 device, then the address should be set to 2. A total of 8 devices may be connected.
lite blue
Address
1
2
3
4
5
6
7
8
After the AD-300 has been connected to the lite blue controller, make a note of the channel and address. This
information will be required to set up the lock in the software.
For additional information on the Schlage Utility Software see the

To address the AD-300 lock:

Start
1
Click
on the PDA. A Menu will open with a list of programs.
Schlage Utility Software
2
Select the
Manager
3
Select
4
Enter the password into the
Login
5
Click the
Connected.
6
Connect the PDA to the AD-300 lock using the supplied USB cable.
Schlage
7
Press the
AD300.
Options
8
Click on the
VLBIM06/15/15 v4.1.0
.
SUS Address
0
1
2
3
4
5
6
7
option to open
Log on as
from the
drop down menu.
Password
field. Default password is
button. The SUS program will open. The bottom of the screen will say
button twice on the AD-300 keypad. The bottom of the PDA screen will now display
button at the bottom of the PDA screen. A list of options will open.
lite blue
uses an address list of 1 through 8. When
Schlage Utility Software User's Guide
SUS
.
123456
89
.
No Device