7.6.3

Output Setting

Path:
→ Output Setting
Item
Voltage
Voltage
Compensation
Frequency
Slew Rate
Power Module
Redundancy
Asynchronous
Transfer Time
Module
Sequential Start
System
Sequential Start
Ultron DPS Series
Set up the output voltage.
When the UPS is distant from the loads and there is a voltage drop
in the output, you can adjust the INV output voltage amplitude for
voltage compensation.
Set up the output frequency as 50Hz (default) or 60Hz. The system
will automatically select the output frequency in accordance with the
bypass power.
Set up the maximum permissible speed for the system output
frequency to catch up the bypass frequency variation.
Set up how many power modules that need to be preserved for
redundancy.
When it is impossible for the inverter to reach synchronous phase
lock with the bypass, the output will be terminated during
conversion process according to this setup time.
Set up the time interval for every power module to be converted
from the Battery mode to On-Line mode. The setup is applicable to
the generator to avoid bearing the whole loads right away.
Set up the time interval for the system to be converted from the
Battery mode to On-Line mode. The setup is applicable to the
generator to avoid bearing the whole loads right away.
Description
128