Using Dual Rtps To Field Wiring The 16 Point Ai; Analog Input Accuracy Specification - Honeywell ControlEdge 900 platform Hardware Planning And Installation Manual

Controledge plc, controledge rtu
Hide thumbs Also See for ControlEdge 900 platform:
Table of Contents

Advertisement

Appendix A - Installing RTP
Table A-2: Analog Input accuracy specification
Range
100Ω Plat. RTD
JIS RTD
10Ω Cu. RTD
200Ω OHMS
0-10mV LINEAR

Using Dual RTPs to field wiring the 16 Point AI

To wire the 16 Point AC AI using two RTPs:
1. Mount the RTP cable assembly to ControlEdge 900 Controller. See the
196
AI Module Accuracy
±0.1% of Range
±0.1% of Range
±0.1% of Range
±0.1% of Range
±0.1% of Range
ATTENTION:
RTP and cables are intended for permanent installation within their own
l
enclosure.
The RTP labeled "DI, DO, AO RTP ASSY" with jumpers J2-J9 is the correct
l
one for 16 point AI.
following figure for the example installation diagram.
RTP + Cable Accuracy
±0.04% Range (0.357°C)
±0.12% Range (0.824°C)
±0.57% Range (1.540°C)
±0.07% Range (0.140Ω)
±0.04% Range (0.004mV)
AI Module + RTP Accuracy
±0.14% of Range
±0.22% of Range
±0.67% of Range
±0.17% of Range
±0.14% of Range