SDC+ refers to switched positive side of the DC supply.
l
Terminals 9 and 11 (DC-) are connected through the RTP cable. Same for
l
terminals 10 and 12 (DC-).

Using an RTP to field wiring the 8 Point AC DO

ATTENTION:
RTP and cables are intended for permanent installation within their own
l
enclosure.
8 point AC Output is limited to maximum of 2A per output for any VAC, 6A
l
per RTP for 240VAC, 8A per RTP for 120VAC.
The RTP combines the 8 isolated outputs into one group of 8.
l
To wire the 8 Point AC DO using an RTP:
1. Mount the RTP cable assembly to ControlEdge 900 Controller. See the
following figure for the example installation diagram.
Appendix A - Installing RTP
207