For Canada; For Atex - Honeywell ControlEdge 900 platform Hardware Planning And Installation Manual

Controledge plc, controledge rtu
Hide thumbs Also See for ControlEdge 900 platform:
Table of Contents

Advertisement

Chapter 9 - Special Condition of Use and Approved Standards
180
Equipment shall be installed in compliance with the enclosure,
n
mounting, spacing and segregation requirements of the ultimate
application.
For installation with a second active phase (L-L) instead of neutral
n
(L-N) connection both phases must be protected externally with
circuit breaker adequately rated for 3 A maximum and 250 V AC
minimum.

For Canada

The installer shall provide transient over-voltage protection
n
external to the apparatus such that the voltage at the supply
terminal of the apparatus does not exceed 140% of the voltage
rating of the equipment.
The equipment shall be mounted in an enclosure providing a
n
minimum degree of protection of IP54 in accordance with
CAN/CSA 60529., and in a tool-secured enclosure which meets the
requirements of CAN/CSA 60079-0 and CAN/CSA 60079-15.
Equipment shall be installed in compliance with the enclosure,
n
mounting, spacing and segregation requirements of the ultimate
application.

For ATEX

The installer shall provide transient over-voltage protection
n
external to the apparatus such that the voltage at the supply
terminal of the apparatus does not exceed 140% of the voltage
rating of the equipment.
The equipment shall be mounted in an enclosure providing a
n
minimum degree of protection of IP54 in accordance with
EN/IEC 60079-15.
The equipment shall be mounted in a tool-secured enclosure
n
which meets the requirements of EN/IEC 60079-0 and EN/IEC
60079-15.
The equipment shall be used in an area not more than Pollution
n
Degree 2 as defined in EN/IEC 60664-1.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents