Module
* The field device is powered by external 24 V power supply. For more information,
see
Universal Input/Output Module

Environmental considerations

The product is only used indoors. The CPM must be mounted in
suitable equipment enclosures. That is, all components such as the
Redundant Controller Rack and I/O rack manufactured by Honeywell
must be mounted in approved furniture designed for industrial
applications.
Consideration should be given to the installation so that the potential
for the build-up of static electricity is minimized or eliminated.
Table 5-8: Environmental specifications
Item
Operating temperature
Storage and transportation
temperature
Ambient Relative Humidity
Vibration (Operative)
Shock (Operative)
Protection against corrosive
atmospheres (for offshore
installations)
Altitude
B: Max
A: Enter
Current
Quantity
@ 5V
on section.
Description
0 to 60 °C
-40 to 85 °C
5% to 95% relative humidity (non-condensing)
IEC 60068-2-6 Sinusoidal (5 to 8.4 Hz) 3.5mm /
(8.4 to 150 Hz) 1.0 g; 1 octave/min, 10 cycles per
axis, 3 axes.
Half-sine, 15g peak / 11 ms duration, 6 directions
ANSI/ISA S71.04 Class G3
2000 meters
D:
C: Max
Calculate
Current
5V current
@ 24V
(D = A * B)
Total mA
@ 5V - ( )
E:
Calculate
24V
current (E
= A * C)
Total mA @
24V - ( )
81