AWG
Diameter
No.
inches
30
0.0100
Table values are shown as a reference only; actual values may vary. Consult
manufacturer specifications.
122
Type
Type
Type T
K
J
5.984 3.551 3.043

Isolation

This module has eight inputs, which are isolated except for RTD
current sources.

RTD Inputs

RTD inputs share current sources (two RTD inputs per source), as
shown below:
Figure 5-30: RTD Inputs
For example, the current source for the RTD input at channel one
(terminals 1 and 2) is terminal 3 (IRTD 1 & 2). This same current
source (IRTD 1 & 2) is also used for an RTD input at channel two
(terminals 4 and 5).
Figure on
RTD Inputs
(UAI) Wiring
shows the examples of RTD input wiring (2-wire and 3-
wire RTDs). Four-wire RTD inputs are not available.
Type S
Type
Pt/
E
PT110
7.169 1.85
and Figure on
Universal Analog Input Module
Type R
Type
Type
Pt/
W5/
W/
PT113
W26
W26
1.91
2.38
2.03