Led Failure Definition - Honeywell ControlEdge 900 platform Hardware Planning And Installation Manual

Controledge plc, controledge rtu
Hide thumbs Also See for ControlEdge 900 platform:
Table of Contents

Advertisement

Chapter 8 - Diagnostics and Troubleshooting
Number
of
Failure
strobes
1
Failsafe
2
HW/SW
Key
174

LED Failure Definition

Description
The module is in
the failsafe state
because it is not
receiving
message
requests from
the CPU or the
whole system is
in exception
stop.
The software
residing on the
module does
not match the
module type.
This diagnostic
should only
result in the
factory.
User Action
1. If expansion I/O rack, go to step
2. If non expansion I/O rack, go
to step 3.
2. Check the Scanner status LED If
it's flashing 6 times, proceed
with step 3. If it's flashing some
other red status code, refer to
Table 29 to solve that problem
first. If it's flashing green, the
module probably is not required
in the configuration. If it's not on
or steady, cycle power to the
scanner.
3. Make sure the module is the
correct one for the
configuration.
4. Remove the module and check
for a bent pin, then reinsert the
module
5. Replace the module
6. Remove other modules and
replace one at a time until the
problem reoccurs. Most likely the
last module inserted needs to be
replaced.
7. Replace the rack.
Replace module
Applies
to
All
modules
DI and
Relay
DO and
DC DO