Dip Swith Position Of 8 Channel Ao; 8 Channel Analog Output Wiring Diagram - Honeywell ControlEdge 900 platform Hardware Planning And Installation Manual

Controledge plc, controledge rtu
Hide thumbs Also See for ControlEdge 900 platform:
Table of Contents

Advertisement

142
CAUTION:
Hazardous voltages
Using switches at field devices disconnect the field wiring form
power sources before servicing.
Failure to comply with these instructions could result in death or
serious injury.
If installing 8 channel Analog Output module, set its DIP switch as
follows. (Switch is located at edge of module, marked "SW1".)
For internal rack power, set DIP switch to ON.
n
For external power (18-36V), set DIP switch to OFF (default).
n
NOTE: 24VDC external power is required if using 6 or more 8-pt.
AO modules or 3 or more 16-pt. AO modules.
A small slotted screwdriver or paperclip works well; avoid using
pencils.
Figure 5-54: Dip Swith Position of 8 Channel AO
Figure 5-55: 8 Channel Analog Output Wiring Diagram
exist at terminal blocks.