I/O Module Specification

ControlEdge PLC supports various input/output modules. This
section provides technical information to configure ControlEdge PLC
IO Modules. The following IO modules are included:
Universal Input/output module, 16 channel
n
Universal AI – RTD,TC,V 8 Channel
n
Analog Input High Level, 16 Channel
n
Analog Output, 4 Channel
n
Analog Output, 8 Channel
n
Digital Input 120/240 VAC, 16 Channel
n
Digital Input 24 VDC, 32 Channel
n
Digital Input Contact, 16 Channel
n
Digital Input 120/240 VAC, 125 VDC (16 Channel Isolated)
n
Digital Output 120/240 VAC, 16 Channel
n
Digital Output 24 VDC, 32 Channel
n
Digital Relay Output, 8 Channel
n
Pulse/Frequency/Quadrature, 4 Channel
n
See ControlEdge PLC Specification for details.

Universal Input/Output Module

The maximum current of the Universal Input/Output Module (UIO)
field side is 4.2 A.
One UIO module provides a 20-terminal block with 16 channels, and
it can be connected with two external 24 V DC power supplies. At least
one power supply must be connected.
See
UIO module wiring
UIO module supports:
16 Channel, each channel can be configured for AI, AO, DI & DO
n
Analog Input (AI), 0-20 mA
l
Analog Input (AI) with open wire detection, 4-20 mA
l
Analog Output (AO), 4-20 mA, See
l
Output
section for channel restrictions on the same UIO
module.
Digital Input (DI) with line monitoring
l
Digital Output (DO) with short circuit protection
l
section.