Using an RTP to field wiring 4 Channel Analog Output

To wire the 4 Channel Analog Output using an RTP:
1. Mount the RTP cable assembly to ControlEdge 900 Controller. See the
212
SDC- refers to the switched negative side of the DC supply.
l
Terminals 9 and 11 (DC-) are connected through the RTP cable. Same for
l
terminals 10 and 12 (DC+).
ATTENTION: RTP and cables are intended for permanent installation within
their own enclosure.
following figure for the example installation diagram.